Request
More Information on this Model
|
|
|
|
|
| Series |
LBT |
| UPS
Type |
Line
Interactive Long Backup Time UPS |
| Power
Range |
600
VA |
|
 |
The lightest
UPS in the world with the longest discharge time |
 |
Built-in
Automatic Voltage Regulator (AVR) and Surge Protection circuitry to
protect any damages from lightening and unstable power input. |
 |
Discharge
time can be extended, when an extra stackable type battery pack is
added. (Battery packs can be stacked up to 5 sets) |
 |
Perfect
for home appliances such as, TV, VCR, Fax Machine, Combo Stereo system,
Electrical Fan, Table Lamp, fish tank pump, etc. |
 |
Fully
automatic, no complicated operations needed. |
 |
Fully
digitalized micoprocessor controlled operations needed. |
 |
Stylish
design with front panel LED displaying line-input, Load and Battery
status |
 |
Cold
start without AC input to be operated during a power outage |
 |
Low
noise compared with a generator |
| Model
|
LBT-600A |
LBT-600A
RM |
| Power Rating |
600
VA |
| Input |
| Voltage |
+/-25%
at line input |
| Capacity |
600
VA |
| Frequency |
50
o 60 Hz +/- 10% (auto sensing) |
| Output |
| Volatge (on Battery) |
Simulated
sine wave at 100V/115V/230V +/- 5% |
| Frequency (on Battery)
|
50
or 60 Hz +/- 0.5% |
| Voltage Regulation |
AVR
automatically increases output voltage 15% above input voltage, if
-9% to -25% of nominal. AVR decreases output voltage 13% below input
voltage, if +9% to +25% of nominal |
| Transfer Time |
2/4
milliseconds, including detection time |
| Protection
and Filtering |
| Spike
Protection |
80
Joules, 2ms |
| Overload
Protection |
UPS
automatic shutdown if overload exceeds110% of nominal at 60 seconds
and 130% at 3 seconds |
| Unit
Input |
Fuse
for overload & short circuit protection |
| Short
Circuit |
UPS
output cut off immediately or input fuse protection |
| Back-up
Time |
| PC |
2
Hours |
| PBX
(100 W) |
4
Hours |
| Fax
Machine (40 W) |
13.5
hours |
| Battery |
| No.
of built-in battery |
4
|
1,2,3,4
(optional) |
| Type |
Sealed,
Maintainence-free lead acid |
| Recharge
Time |
6
hours typically (to 90% of full capacity) |
| Protection |
Automatic
self-test & discharge protection, replace battery indicator |
| Additional
Battery pack |
1 |
| DC
Voltage |
12V
(DC) |
| Alarm
Type |
| Battery
Back-up |
Slow
beeping sound (about 0.47 Hz) |
| Battery
Low |
Rapid
beeping sound (about 1.824 Hz) |
| Overload |
Continue
beeping sound |
| Environment |
| Temperature |
0°
C to 48° C |
| Humidity |
0%
to 95% (non-condensing) |
| Mechanical |
|
Main Unit |
Weight/net(kgs) |
17.5
|
| Dimension(WxDxH) |
360
x 340 x 91 |
|
Battery Pack |
Weight/net(kgs) |
17.5 |
| Dimension(WxDxH) |
360
x 340 x 91 |
|