Online Uninterruptible Power Supply
-
 
Request More Information on this Model
Name*
Company
Address*
Country*
Phones*
Fax
E-mail*
UserType*
Inquiry
  Fields marked with '*' are required.
     
-
Series ENS3
UPS Type True Online 3 Phase
Power Range 10 KVA to 20 KVA
-
Features
Sinewave Pulse Width Modulation (SPWM)
IGBT inverter design
Double conversion on-line system
Microprocessor control
Smart RS-232 communication port
SNMP management capability
Wide Input Voltage Windows (+/- 25%)
Pure sinewave output less than 3% THD
Versatile, modular design
Expandable battery run time
Generator compatible
Cold Start (DC power on)
Load/Battery power meter display
Overload, on-line, battery status LED
Advanced Battery Management (ABM)
Automatically charging in UPS off mode
20 KHz SPWM high frequency inverter.
-
Product Specifications
Model ENS3-10KS31 ENS3-10S31 ENS3-20KS31
Power Range 10KVA/8KW 15KVA/12KW 20KVA/16W
Input
Voltage, Phase 220V/380V, 120v/208v(2 § 4W), 220V/220V(3 § 3W)
Frequency 50/60 HZ +/- 5%
DC Voltage 192Vdc 360Vdc
Output
Voltage (+/-5% adjustable) 220V, 230V, 240V 1 § 2W
or 110V/220V, 115V/230V, 120V/240V 1 § 3W
Voltage Regulation +/- 1%
Frequency 50 or 60Hz
Frequency Stability +/- 0.5%
Efficiency Whole 84%
Inverter: 90%
Total Harmonic Distortion Less than 3% at linear load
Power Factor 0.8 ~ 1.0 Lagging
Slew Rate <1Hz/Sec
Overload Detection 125% to 150% for 20 seconds
150% for 10 cycle
Crest Factor 3:1
Inverter Operation SPWM (Sinewave pulse wih modulation)
Transient Response +/- 4% for 100% instantaneous load variation
Recovery to +- 1% of rated voltage within 2 ms
Transfer
Power Failure and Recovery 0 ms
Overload disappear Auto transfer to UPS
Bypass Uninterrupted transfer of 100% load from UPS to bypass and vice versa
Alarm
Battery Discharge The first warning will every 4 seconds to indicate battery in use. The second warning will beep every 1 second to signal battery low condition.
UPS Fault Continuos beeping sound
Efficiency
Whole >84%
Inverter >90%
Environment
Operating Temprature 0°C to 40°C
Relative Humidity 0% ~ 95% (Non condensing)
Noise Level <60dB at 1 meter distance
Battery
Back-up time 6-30 minutes (depending on computer load)
Type Sealed Maintenance Free
Protection Cut off without draining any current when battery low
Recharge Time About 8 hours to 90 % after fully discharged
Mechanical (Without Battery)
Dimensions (WxDxH)mm 350x640x970
Weight (Kg) 160 175 215
Other Options
Interface Supporst both RS-232 & dry contact signal to provide power management & dignostic functions including power status, battery low, schedule UPS ON/OFF, battery/load level display and more. Compatible with Windows NT, Novell, AS-400 and SNMP.
-
-
Copyright © 2000, American Micronic Instruments, Inc., USA