Request
More Information on this Model
|
|
|
|
|
| Series |
LCD |
| UPS
Type |
True
Online |
| Power
Range |
1000
VA to 12 KVA |
|
 |
LCD display
front panel |
 |
Double
CPU control |
 |
Cold
start (DC power on) |
 |
True
online double conversion design |
 |
Pure
sinewave output less than 3% THD |
 |
Wide
input voltage range +/-27% of nominal |
 |
Versatile,
modular design provides flexibility during setup and service |
 |
Smart
RS-232 communication port |
 |
SNMP
management capabilty |
 |
Management
software compatible |
 |
Power
factor correction |
 |
Overload
& short-circuit protection |
 |
Load
and battery status indicator |
 |
Fan
speed auto control when load varies |
 |
Extended
backup time with battery pack |
 |
Advanced
battery management (ABM) |
 |
Battery
power & load meter display |
 |
Compact
size, light weight & low noise |
| Model
|
LCD1000 |
LCD2000 |
LCD3000 |
LCD6000 |
LCD8000 |
LCD10000 |
| Power
Range |
1000VA |
2000VA |
3000VA |
6000VA |
8000VA |
10
KVA |
| Input |
| Voltage
|
100V
: 76V ~ 130V, 110 : 80 ~ 138V, 115V : 83.5V ~ 140V, 120V:87V~140V,
208V:152V~260V, 220V: 160V~280V, 240V:174V~280V |
170
~ 276V |
176~276V |
| Frequency |
50/60 HZ +/- 5% |
| Power
factor |
>=
0.98 |
>=0.97 |
| Phase |
Single
Phase |
| Output |
| Voltage |
100/110/115/120
V or 208/220/230/240V |
110/220 |
| Phase |
Single
Phase |
| Voltage
Regulation |
+/-
2%(except LCD3000/110V +/-3%) |
| Frequency |
50/60Hz
+/-0.5% |
| Frequency
Stability |
+/-
0.5% |
| Efficiency |
Whole
84% |
| Inverter:
90% |
| Total
Harmonic Distortion |
Less
than 3% at linear load |
| Power
Factor |
0.7
Lagging |
| Overload
Detection |
105%
for 10 Seconds |
| 130%
+/-10% for 300ms |
| Transfer |
| Power Failure
and Recovery |
0
ms |
| Overload disappear |
Auto
transfer to UPS |
| Bypass |
0
ms |
| Alarm |
| Battery Discharge
|
The
first warning will every 4 seconds to indicate battery in use. The
second warning will beep every 1 second to signal battery low condition. |
| UPS Fault |
Continuos
beeping sound |
| LCD
Indicators |
| Status |
Indicate
line, bypass, iv, backup, fault, bat capacity, load capacity, I/P
voltage, I/P frequency, O/P voltage, inside temprature, fault status |
| Environment |
| Operating
Temprature |
0°C
to 40°C |
| Relative
Humidity |
0%
~ 95% (Non condensing) |
| Noise
Level |
<45dBA |
<52dBA |
<47dBA |
<55dBA |
| Mechanical
(Without Battery) |
| Dimensions (WxDxH)mm |
145x400x220 |
192x460x385 |
260x555x700 |
| Weight
(Kg) |
11.3 |
28.1 |
33.3 |
114 |
250 |
| Other
Options |
| Remote
Panel |
LCD
Indication for the status of the rectifier, battery, inverter and
output load |
| Interface |
Supporst
both RS-232 & dry contact signal to provide power management &
dignostic functions including power status, battery low, schedule
UPS ON/OFF, battery/load level display and more. Compatible with Windows
NT, Novell, AS-400 and SNMP. |
|